background image

 
© Eco Heat Equipment

 – 

January 2016

 

                                                                     1 of 2 

 

ES608B HF Motion Sensor User Manual 
 

 

General 

The  ES608B  is  an  active  motion  sensor  that  emits  high-frequency  waves  (5.8GHz). 
The sensor detects the change in the echo return, and is sensitive to movement in 

its detection zone. 

 

 

The ES608B is designed to be used in a device or system and must not be operated 

without appropriate protective covering.  

If, after reviewing this guide, you require additional information or assistance 

please contact Eco Heat Equipment at [email protected], +27 (0)861 999 887, 

or www.ecosensor.co.za.  
 

Technical Specifications 

§

 

Voltage: 220 – 240V/AC 

§

 

Frequency:  50/60Hz 

§

 

Working temperature: -15°C to 70°C 

§

 

Load:  Incandescent max: 1 000W  

            Fluorescent max: 600W 

            LED max: 300W 

§

 

Detection Range: 2 – 10m  

§

 

Detection Angle: 360° 

§

 

Light level: 10 – 500 LUX 

§

 

Time setting: 10 seconds – 30 minutes 

§

 

Installation height: 2 – 10m  

§

 

Motion Sensor HF system: 5.8GHz CW radar, ISM band 

§

 

Motion Sensor transmission power:  <0.2mW RF power 

§

 

Dimensions: 60mm* (L) x 41mm (W) x 28.5mm(H)  

(* excludes mounting foot – total length 65.5mm) 

 

 

Safety 

Any  incorrect  use  or  installation  procedure  not  recommended  by  the 

manufacturer may cause fire, electrical shock or injury to persons. 

 

 

Box Contents  

Your box should contain the following items: 

§

 

HF Sensor 

 

 
WARNING:  

Controlling a load in excess of the specified ratings will damage the unit and lights 

and could pose risk of fire and electric shock. 

 

Do not install this unit to control a power socket.

 

 

Installation Instructions 

WARNING: THE ES608B IS DESIGNED TO BE A COMPONENT IN A DEVICE OR SYSTEM 

AND IS NOT SUITABLE TO BE USED IN ITS CURRENT FORM. ENSURE THE USE OF THE 

ES608B IS IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES AND 
STANDARDS. 

 

Note: Do not install the motion sensor on unstable or vibrating surfaces, or near 

doors and windows where outside movement may be detected. Motion may be 

detected through ceilings, drywall, wood or plastic.  

Sensor calibration: 

Note:  Allow  up  to  1  minute  for  the  motion  sensor  to  recalibrate  after  it  has  been 
connected for the very first time. This is only necessary during installation or when 

the mains supply is disconnected.  

 

Note: After the connected device switches OFF, it takes approximately 4 seconds 
before it is able to start detecting movement again. The connected device will 

only switch on in response to movement once this period has elapsed. 

 

 

 
 

 

 

 

 
 

 

 

 

 
 

Wire diagram 

 

 

 

Operation and Field of View

 

The  motion  sensor  detects  motion  within  its  coverage  area  and  controls  the 
associated  load  connected  to  the  sensor.  For  best  performance,  persons  or 

objects  moving  towards  the  sensor  are  ideal.  Detection  is  possible  through 

wooden doors, panes of glass, dry wall, ceiling tiles, or thin brick walls. Beware of 

windows facing passages or roads. 

 

 

Ceiling Mount

 

 

 

 

 

Wall Mount (side view) 

 

 
 

Wall Mount (top view) 

 

 
 

Motion Sensor Settings and Adjustments 

The  motion  sensor  is  a  high  frequency  (HF)  type  electronic  occupancy  detector, 

which  in  turn  switches  a  load  when  connected  to  the  motion  sensor.  There  are 

three  adjustments  that  can  be  made  to  influence  the  operation  of  the  motion 
sensor:  

1.

 

RANGE: motion detection range 

2.

 

TIME: time delay after motion until shut off 

3.

 

LUX/LIGHT: level of ambient light sensitivity 

 

Отзывы: