Service parameter’s list
Display Parameter
Min
Max
Step
Factory
default
N100
fan power or max fan power when Nr 1
50
100
10%
100
N
% of fan ramp down
Nh
degrees ramp down starts
Nr 1
automatic fan speed control
- .0
10
1
1
Nn 5
fan work time
- .5
60
1s
5
Nu 6
fan pause time
1
99
1min 6
P144
circulating pump launch temperature
85
160
1°F
144
Ph 4
circulating pump launch hysteresis
2
20
1°F
4
Pc 2
pause time between circ. Pump 30 secs.
work periods
- .1
99
1min 2
L150
min boiler temperature
85
150
5°F
150
H195
max boiler temperature
175
195
5°F
195
h 10
boiler temperature hysteresis
2
20
1°F
10
A210
boiler overheating temperature
195
210
1°F
210
Fd60
no-fuel testing time during fuel firing start
- .1
99-4h 1min 60
Fb30
no-fuel testing time during work mode
- .1
99-4h 1min 30
Ar 0
additional output: 0-FUEL, 1-ALARM, 2-MIX 0
2
1
0
Prod
return to factory settings after pressing OK
outP
test of circ. Pump output
(press OK to launch the test)
outP out1
outN
test of fan output
(press OK to launch the test)
outN out2
outr
test of additional output
(press OK to launch the test)
outr
out3
End
quit service mode after pressing OK
In the table above, the first column represents example display indications, in the next columns you have: parameter description,
minimal amount, maximum amount allowed to set, step of the parameter during the setup, factory defaults, to which you can return by
choosing the [Prod] option.
b)
Pressure fan work parameters
Fan power
[Π100]
- this value defines power of the fan. When "Πr" parameter is set to
"0-10"
this is the maximum power of the fan
which can be achieved during the automatic fan control.
Automatic fan speed control
[Πr 1]
– it’s on, when this parameter is set to
"0-10"
and causes automatic fan speed reduction when the temperature of water in the boiler reaches the desired temperature. If this
parameter is set to
"-"
, the fan automatic smooth speed control is disabled and the fan can work with power set by
"Π"
parameter.
Setting parameter value in range from 0 to 10 means time in minutes of the smooth fan speed increase from 40% to a value of
"Π"
for
a smooth boiler start.
Fan work time
[Πn 5]
- time of turning the fan on for a while, to remove accumulated gases. Setting the parameter to
"-"
turns this
function off.
c) Circulating pump parameters
Circulating pump launch temperature
[P144]
- temperature of water in the boiler, which causes start of the circulating pump.
Circulating pump works independently from the control process and is launched additionally in case of boiler overheat.
Circulating pump launch hysteresis
[Ph 4]
- this parameter defines what value should temperature decrease by, below circulating
pump launch temperature, to turn the pump off.
Pause time between circulating pump 30 second work periods
[Pc 2]
- in
STOP
mode or when room thermostat circuit is open; the circulating pump is launched for 30 seconds, to mix water in heating
circulation. This parameter defines time between launches of the pump.
Setting the parameter to
"-"
turns this function off.