36
Notes:
•
Connections on the water heater side should
always
be executed as drawn in the picture above.
•
1
Always apply safety components according to all applicable regulations.
•
2
In case of more than one tank, mount the tank sensor on one of the tank outlets. The temperature of
this tank will be assumed to be representative for all, provided that the installation design is correct.
•
In the inlet (return) connection of the water heater no check valve is recommended.
•
If needed, the water heater control can handle up to twelve water heaters.
•
For large capacity installations consult your supplier.
8.1.6
C
ASCADE CALCULATIONS
CB-HW water heaters and tanks can be cascaded in a number of possible combinations according to the instruc-
tions below. Pipe sizes should be selected conforming to the tables A, B and C below. These are minimum (cop-
per) pipe sizes; selecting smaller pipes will result in a higher water resistance of the system, in higher temperature
differences between flow and return of the boiler, and in a higher risk of calcification of the system.
Table
A: Connections directly on the water heater(s)
Diameters D1 ( = OUTLET and INLET of each water heater)
(42 x 1,5 = Outside diameter mm x wall thickness mm e.g.)
ΔT = 16.5°C
ΔT = 12.5°C
CB 85 HW
42
1.5
42 x 1.5
CB 105 HW
54 x 1.5
CB 125 HW
CB 155 HW
54
1.5
Example of a combination of three boilers and two non-EWD tanks
Water
heater
Water
heater
Water
heater
Содержание CB 105 HW
Страница 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Страница 70: ...E93 1803 901 HW 71...
Страница 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Страница 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Страница 128: ...E93 1803 901 HW 129...
Страница 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Страница 130: ...E93 1803 901 HW 131...
Страница 145: ......
Страница 146: ......