Firmware V1.4
20.05.2021
79/113
7.2.1 Terminal Assignment of the Analogue Inputs
Analogue inputs Pt1000 (Pt1..15)
DANGER
Warning of dangerous electrical voltage! Danger to life - Danger of electric shock!
If supply
voltage is connected to the analogue inputs, there is a risk of personal injury as the analogue inputs
are not galvanically isolated from other system components (e.g. pressure transmitters). Furthermore,
this will destroy the controller!
•
•
•
ATTENTION
Malfunction due to interference!
All supply lines from and to the controller (with the exception of the
230 V supply and signal lines) must be shielded (cable type: LiYCY)! This particularly applies for the
analogue inputs and outputs (e.g. sensor supply lines). As a general rule, care should be taken to
ensure that signal cables and cables carrying mains voltage are routed in separate cable ducts.
Furthermore, the following must be observed when installing the analogue inputs:
Correct sensor positioning
Correct fixing of the sensors by using metal clamps and thermally conductive paste
Insulation of the sensors (e.g. protect sensors against direct exposure to sunlight)