Firmware V1.4
20.05.2021
69/113
•
•
•
7 Pin and Terminal Assignments of WRG 3010 E
The following figures and tables show the terminal assignments of the basic module and the SIOX extension
modules.
Basic module GLT x010 in full extension with max. 3 SIOX extension modules. For more details, see chapters
Connections for 230 V AC (top)
Connections for Protective Extra-Low Voltage (bottom)
Connections for Interfaces (on the side)
•
•
•
DANGER
Warning of dangerous electrical voltage! Danger to life - risk of electric shock or malfunction!
The following points must be
strictly
observed when wiring:
Before
loosening or inserting plug contacts on the controller, the system must be
disconnected
from the power supply
!
For
analogue inputs and outputs
with current or voltage interface (4..20 mA / 0..10 V), it is
essential to ensure
correct polarity
. Short circuits or a faulty power supply can result in
impairments of the function or even destruction of components of the controller.
All
connection cables
from and to the controller - with the exception of the relay outputs and
digital inputs - must be
shielded
. Otherwise malfunctions, e.g. faulty measurements, cannot be
ruled out.