Firmware V1.4
20.05.2021
49/113
6.1 Top-Hat Rail Mounting
The basic module and the SIOX extension modules are snapped onto a top-hat rail by means of two claws on
the back; for details see chapter
.
Specified mounting position
The basic module must be mounted as follows:
Protection class and dimensions see chapter
ATTENTION
The controller may only be operated mounted on a top-hat rail as a built-in regulating and control unit
(EN60730) and can be bayed without spacing. The power dissipation of the controller is 24 W and 3.1
W per SIOX. To operate the controller, the natural convection of the circulating air with free air
exchange is sufficient to avoid overheating. A sufficient air inlet under the unit (min. 30 mm) and an
unobstructed air outlet above it
must
always be ensured. If this cannot be guaranteed, forced
ventilation is required!
All supply lines from and to the device (with the exception of the 230 V power supply and signal lines)
must be shielded! This applies in particular to the analogue inputs and outputs as well as to the CAN
bus and Modbus wiring; see operating instructions
"
Basics and General Safety and Connection
". These must also be installed with sufficiently large distance from live cables. As a general
rule, care should be taken to ensure that signal cables and cables carrying mains voltage are routed in
separate cable ducts.
Содержание WRG 3010 E
Страница 70: ...Firmware V1 4 20 05 2021 70 113 7 1 Connections for 230 V AC top Basic Module SIOX Extension Module...
Страница 78: ...Firmware V1 4 20 05 2021 78 113 7 2 Connections for Protective Extra Low Voltage bottom...
Страница 84: ...Firmware V1 4 20 05 2021 84 113 7 3 Connections for Interfaces on the side Basic Module SIOX Extension Module...
Страница 103: ...Firmware V1 4 20 05 2021 103 113...