Firmware V1.4
20.05.2021
43/113
•
•
•
•
•
•
•
Setpoints
Parameter in
LDSWin *
Description
Value
range
Default
value
Visualisation in LDSWin - HT / LT / Power Signal Setpoints
LWP Ein
Threshold value of the power signal for switching on the air heat pump, if Überschreitung Ein.
0.1..12
V
9.5 V
LWP Aus
Threshold value of the power signal for switching off the air heat pump, if Überschreitung Aus.
0.1..12
V
9.2 V
Visualisation in LDSWin - GCBP / LWP / air conditioning operation setpoints
LWP
vorhanden
Button for selecting the LWP.
YES: the air heat pump is available.
NO: the air heat pump is not available.
YES /
NO
NO
LWP
Einschaltverz
ug **
Delay time for heat pump enable.
The WRG 3010 E switches to the operating mode "LWP" if the calculated power signal has
reached the switch-on threshold. This parameter can then be used to delay the start of the air
heat pump again.
0..600
min
60 min
LWP max
HGtemperatu
r
Maximum outlet temperature of the hot gas from HT heat exchanger. Exceeding this temperature will
cause the LWP to switch off, even if the power signal requests the LWP.
The LWP is not enabled again until the hot gas outlet temperature drops 4 Kelvin below this threshold.
20.0..80
.0 °C
40.0 °C
Visualisation in LDSWin - GCBP / LWP / air conditioning operation setpoints
Abtau
Intervall
The defrost interval specifies the time period for which the LWP must be in operation before the next
defrost is started.
60..144
0 min
360 min
Abtau
Endtemperat
ur
If the defrost termination temperature sensor in the LWP reaches this value, the defrost will be
terminated.
1..25 °C
15 °C
LWP
Abtauzeit
This parameter specifies the maximum defrost time, after which defrosting is ended and the drip time
starts.
1..120
min
60 min
LWP
Abtropfzeit
The drip time is used to drip/dry the LWP package before the LWP is put back into operation.
1..10
min
5 min
LWP
Handabtauun
g
Button for initiating the defrost.
YES: start defrost process.
NEIN: do not start a manual defrost.
YES /
NO
YES
Abtauung
WRG aus
Button for switching off the heat recovery during the defrost process.
YES: the heat recovery is deactivated during defrosting in order to use all the available heat of
the refrigeration pack system for defrosting.
NO: heat recovery is throttled during defrosting by the heating instances GCBP and LWP.
YES /
NO
YES
* The name of the parameter is displayed as a tooltip when the mouse is moved over the setpoint.
** Parameter is applicable for heat recovery HT and LT.
5.10 Archiving of operating data
All relevant operating data of the controller for heat recovery are transmitted via the CAN bus to the system
centre for later system analysis and evaluation in LDSWin and archived there.
Содержание WRG 3010 E
Страница 70: ...Firmware V1 4 20 05 2021 70 113 7 1 Connections for 230 V AC top Basic Module SIOX Extension Module...
Страница 78: ...Firmware V1 4 20 05 2021 78 113 7 2 Connections for Protective Extra Low Voltage bottom...
Страница 84: ...Firmware V1 4 20 05 2021 84 113 7 3 Connections for Interfaces on the side Basic Module SIOX Extension Module...
Страница 103: ...Firmware V1 4 20 05 2021 103 113...