Firmware V1.4
20.05.2021
37/113
5.5 Desuperheating
The first stage of heat recovery is the desuperheating heating instance. If the power signal HT or LT reaches
the respective "Heat On" threshold, the HT or LT function is enabled accordingly. For details, see
and
Low temperature LT heat recovery
.
Setpoints
Parameter in LDSWin *
Description
Value range
Default value
Visualisation in LDSWin - HT / LT / Power Signal Setpoints
Enthitzen Ein
Threshold Enthitzen Ein
0.1..12 V
0.5 V
Enthitzen Aus
Threshold Enthitzen Aus
0.1..12 V
0.3 V
* The name of the parameter is displayed as a tooltip when the mouse is moved over the setpoint.
5.6 Pressure boost
Pressure boosting is implemented by sending a new setpoint value to the
via the CAN bus
depending on the calculated power signal. The new setpoint is shifted linearly between "min HD bei WRG" and
"max HD bei WRG", depending on the power signal.
The voltage value of the power signal can be set with the parameter "Druckanheb. unten", the associated
pressure is set with the parameter "min HD bei WRG".
The voltage value of the power signal can be set with the parameter "Druckanheb. oben", the associated
pressure is set with the parameter "max HD bei WRG".
Setpoints
Parameter in LDSWin *
Description
Value range
Default value
Visualisation in LDSWin - HT / LT / Power Signal Setpoints
Druckanheb. unten
Pressure boost lower threshold
0.1..12 V
1.0 V
Druckanheb. oben
Pressure boost upper threshold
0.1..12 V
6.0 V
min HD bei WRG
Pressure value for the lower threshold of the
pressure boost
40..92 bar
50 bar
max HD bei WRG
Pressure value for the upper threshold of the
pressure boost
40..92 bar
80 bar
* The name of the parameter is displayed as a tooltip when the mouse is moved over the setpoint.
Example:
If "
Druckanheb. unten"
is set to 1 V and
"
Druckanheb. oben"
is set to 6 V, then with a calculated
power signal of 5 V, an HP setpoint of 74 bar is transmitted to the
values of the HP are at the default values.
In addition, a signal is sent via the CAN bus to the Vpack controller, which confirms the validity of the HP
setpoint.
The two parameters "min HD bei WRG" and "max HD bei WRG" influence the HP setpoint which is transmitted
from the WRG 3010 E via the CAN bus to the pack controller. In the pack controller, the received new HP
setpoint is checked for Min and Max; the two parameters are also located there. Ideally the parameters in the
WRG 3010 E should be set to the same values as in the pack controller.
Содержание WRG 3010 E
Страница 70: ...Firmware V1 4 20 05 2021 70 113 7 1 Connections for 230 V AC top Basic Module SIOX Extension Module...
Страница 78: ...Firmware V1 4 20 05 2021 78 113 7 2 Connections for Protective Extra Low Voltage bottom...
Страница 84: ...Firmware V1 4 20 05 2021 84 113 7 3 Connections for Interfaces on the side Basic Module SIOX Extension Module...
Страница 103: ...Firmware V1 4 20 05 2021 103 113...