Firmware V1.4
20.05.2021
88/113
7.3.4 Terminal Assignment of SIOX
Example of
a basic module with one SIOX extension module:
DANGER
Warning of dangerous electrical voltage! Danger to life - Danger of electric shock! BEFORE
connecting and disconnecting, it must be ensured that
no voltage
is present at all connections of the
controller.
ATTENTION
Danger of destruction of components! SIOX extension modules may only
be connected to each
other or the controller when no voltage is present! In the event of an Ethernet network cable with PoE
(Power over Ethernet) being used instead of the SIOX data cable (RJ45) damage can occur to
participating network devices!
Malfunction due to interference!
All supply lines from and to the controller (with the exception of the
230 V supply and signal lines) must be shielded! In general, it must be ensured that signal lines and
lines with mains voltage are routed in separate cable ducts.
SIOX SUPPLY - Power supply*:
Supply lines must have a cross-section of > 0.5 mm
2
. It is
recommended, for example, to use the cable type
LiYCY 4x0.75 mm
2
with 25 Ohm/km.
SIOX data cable*:
Always use CAT5 cables or better, the minimum bending radius (practical value:
bending radius = 4 times diameter) must be observed.
* The maximum permissible length is 30 m!
Содержание WRG 3010 E
Страница 70: ...Firmware V1 4 20 05 2021 70 113 7 1 Connections for 230 V AC top Basic Module SIOX Extension Module...
Страница 78: ...Firmware V1 4 20 05 2021 78 113 7 2 Connections for Protective Extra Low Voltage bottom...
Страница 84: ...Firmware V1 4 20 05 2021 84 113 7 3 Connections for Interfaces on the side Basic Module SIOX Extension Module...