Pt1000
Terminal No.
Function
1, 2, 3, 4
AT (outside temperature)
5, 6, 7, 8
--
* The analogue inputs can also be used in 2-wire technology by bridging the terminals V+ with + or - with -V:
9, 10
T CO2 on HT
11, 12
T CO2 on LT
13, 14
T CO2 off LT
15, 16
T CO2 off HT
17, 18
T H2O Backl. LT
19, 20
T H2O flow LT
21, 22
T H2O return HT
23, 24
T H2O flow HT
25, 26
T H2O return Air conditioning
27, 28
T H2O flow Air conditioning
29, 30
T Buffer HT upper
31, 32
T Buffer HT lower
33, 34
LWP defrost sensor
Note:
The use of temperature sensors in 2-wire technology leads to large measuring errors at long
distances, which can be compensated if necessary; for details see
calibration of Pt1000 temperature