Firmware V1.4
20.05.2021
66/113
The current file for the firmware update is available in the EDP under
https://edp.eckelmann.de/edp/lds/
.
6.6.2 Update of the current firmware
The file "
wrg3010e.exe
" (E) for the firmware update is available in the EDP at
and may have to be unpacked from the ZIP archive
before
use.
The firmware update is performed using a notebook (or PC) that is connected to the controller via the COM port
interface (RS232).
The following steps must be
strictly
performed and observed during the firmware update:
1. Strictly disconnect controller from the mains power supply (there
must
be absence of voltage) .
2. Set DIP switch S1 coding switches
6 and 7 to OFF
:
3. Connect controller (A) to flash cable (B) (connect both 4-pin plug connectors at the terminals 5/6/7/8 and
13/14//15/16).
4. Connect flash cable (B) to null modem cable (C).
5. Connect null modem cable (C) to the COM port (RS232) of the notebook (D)
6. In Windows Explorer, run the file
"GLT3010.exe"
by double clicking on it and select the used COM port on
the screen.