Firmware V1.4
20.05.2021
61/113
6.3.5.1 Status LEDs
Function
Colour
LED
Description
Lower board
LIFE
green
LED
Flashing: Active lamp, controller is supplied with power, processor is running
Off: Power supply interrupted or device defective or no user programme on the controller
POWER
green
LED
On: Power supply OK
Off: Power supply interrupted or device defective
Upper board (internal SIOX)
LIFE
green
LED
FLASHING: Active lamp, circuit board is supplied with voltage, processor is running
OFF: Power supply interrupted or device defective
Relay outputs
green
LED1
..
LED10
ON: Relay is switched
ATTENTION: External voltage may be present at these terminals!
Digital inputs
red
LED1
..
LED23
ON: Digital input is activated, voltage is present!
ATTENTION: External voltage may be present at these terminals!
For future
functions
red
LED
--
DANGER
Warning of dangerous electrical voltage - Danger of electric shock!
The controller must be
disconnected from the power supply before opening the housing. Never operate the controller without
the housing.
Information on the exact terminal assignment can be found in the chapter