Service area (service mode) analogue inputs and outputs
After enabling the service area (service mode), the desired analogue signal can be entered for each analogue
input (AI 1.. AI 7) and output (AO 1..AO 4). The terminal is only enabled after the relevant button (FRG ON) has
been pressed. The corresponding indicator lights up green and the "remaining time" (the time the value remains
active) is displayed:
The service mode for each analogue signal is
automatically ended after 60 minutes
or it can be ended
directly via the button within the 60 minutes. If the time has elapsed or if the service mode is ended directly, the
controller returns to regular operation.
Both the release of the service area and the release of the service mode for each individual analogue signal
(FRG ON) generates a message with prio. 23 in the alarm list.