Firmware V1.4
20.05.2021
35/113
•
•
•
•
Setpoints
Parameter in LDSWin * / **
Description
Value range
Default value
Details see
Visualisation in LDSWin - HT / LT / Power Signal Setpoints
External power signal
HT
Button for switching between external power signal
and internal HT calculation.
ON: external power signal.
OFF: Calculation of the internal power signal
based on the setpoint and the flow and return
temperatures.
ON / OFF
ON
External power signal
LT
Button for switching between external power signal
and internal LT calculation.
ON: external power signal.
OFF: Calculation of the internal power signal
based on the setpoint and the flow and return
temperatures.
ON / OFF
ON
Details see
Visualisation in LDSWin - HT / LT / Power Signal Setpoints
Signal high %
Ramp for power calculation; specifies by how many
percent per time unit the signal should be increased.
0..100%
0.1%
Signal high s
Time unit for the ramp for increasing the power signal.
1..10000 s
100 s
Signal down %
Ramp for the power calculation. The value specifies
by how many percent per time unit the signal should
be reduced.
0..100%
0.1%
Signal down s
Time unit for the ramp for lowering the power signal.
1..10000 s
50 s
Hysteresis power calcul.
Hysteresis for the internal power calculation; details
can be found in the description / diagram.
1..20 K
6 K
Delay pressure boost
Delay until the start of the pressure boost heating
instance. The calculated power signal is frozen while
the time elapses.
0..600 min
5 min
maximum HP
Maximum permitted high pressure. If this value is
exceeded, even if only briefly, all heating instances are
immediately disabled and the calculated power signal
goes to 0. If the high pressure falls below this setpoint
- 5 bar, the heating instances are enabled again.
60..110 bar
100 bar
min. spread CO2
Specifies the minimum spread between hot gas inlet
and hot gas outlet. The value applies for HT and LT. If
the minimum spread is undercut, and this for the delay
time, the calculated power signal is reduced.
5..90 K
5 K
Delay no heating power
If no heating power is present, the calculated power
signal for the relevant heat exchanger (HT / LT) is
reduced to 0 after "Delay no heating power".
0..120 min
10 min
max. HD with WRG
Maximum HP setpoint with power signal "pressure
boost up" or higher.
Note:
This parameter must be set
to the same value in the interconnection controller.
40..92 bar
80 bar
min. HD with WRG
Minimum HP setpoint with power signal "pressure
boost down" or lower.
Note:
This parameter must be
set to the same value in the interconnection controller.
40..92 bar
50 bar
Desuperheat on
Threshold for starting the "Desuperheating" heating
instance; for details, see chapter
0.1..12 V
0.5 V
Desuperheat off
Threshold for stopping the "Desuperheating" heating
instance.
0.1..12 V
0.3 V
Pressure boost down
Lower value for starting the "Pressure Boost" heating
instance; for details, see chapter
0.1..12 V
1.0 V
Pressure boost up
Upper value for "pressure boost" heating instance.
0.1..12 V
6.0 V
GC fan off
Threshold for starting the "Gas cooler fan off" heating
instance; for details, see chapter
.
0.1..12 V
7.0 V
Содержание WRG 3010 E
Страница 70: ...Firmware V1 4 20 05 2021 70 113 7 1 Connections for 230 V AC top Basic Module SIOX Extension Module...
Страница 78: ...Firmware V1 4 20 05 2021 78 113 7 2 Connections for Protective Extra Low Voltage bottom...
Страница 84: ...Firmware V1 4 20 05 2021 84 113 7 3 Connections for Interfaces on the side Basic Module SIOX Extension Module...
Страница 103: ...Firmware V1 4 20 05 2021 103 113...