Firmware V1.4
20.05.2021
31/113
1.
2.
•
•
•
•
•
•
•
•
Setpoints
Parameter in LDSWin
Description
Value range
Default value
Visualisation in LDSWin - WRG 3010 E
Klima Abschalttemp.
The switch-off temperature has 2 functions:
If the water inlet temperature exceeds this
threshold continuously for 10 minutes, the
refrigerant valve is closed. This should prevent
too much flash gas being generated.
The switch-off temperature minus 4 Kelvin is the
setpoint for the speed control of the pump.
10..40 °C
25 °C
Klima Pumpe min
Minimum speed of the pump
0..100%
20%
Klima Pumpe max
Maximum speed of the pump
0..100%
100%
Visualisation in LDSWin - GCBP / LWP / air conditioning operation setpoints
A/C available
Button for selecting the air conditioning mode
YES: the heat exchanger and its peripherals
(pump, refrigerant valve, temperature sensors)
are available.
NO: the heat exchanger and its peripherals are
not available.
YES / NO
NO
Klima Pumpe Kp
Used for setting the Kp of the speed controller of the
pump.
0.01..10
1
Klima Pumpe Tn
Used for setting the Tn of the speed controller of the
pump.
1..32767 s
30 s
WRG-Klima Verr.Zeit
This is the lock-down time between HR mode and A/C
mode.
30..1440 min
30 min
Klima Standzeit
The air conditioning standstill time begins when the air
conditioning is switched off. While this time is running,
the air conditioning operation cannot be switched on
again.
10..240 min
20 min
PV Sauggasüberhitzung
Button for selecting the "PV suction gas superheat"
function.
YES: there are parallel compressors in the
system, and the refrigerant line coming from the
HP valve is routed through an additional heat
exchanger installed in the suction line of the
parallel compressors.
The selection of this option also causes the
GCBP to be enabled with the setpoint "Soll tg1
Klima". In this case, the GCBP is used to ensure
that the temperature of the refrigerant does not
drop below the setpoint. In the case that the
suction gas superheat has been requested and
the GCBP is also requested via the heat
recovery, the setpoint "Soll tg1" from the heat
recovery has priority.
NO: this configuration and this functionality are
not available.
YES / NO
NO
KWS pressure transmitter
Button for selecting the pressure transmitter in the water
circuit.
YES: a pressure transmitter is available, there is
monitoring for wire break.
NO: no pressure transmitter available.
YES / NO
NO
gemein.W-kreislauf
Button for selecting the common water circuit option of
NT and air conditioning.
YES: a common water circuit is available.
NEIN: separate water circuits for LT and air
conditioning are available.
YES / NO
NO
Содержание WRG 3010 E
Страница 70: ...Firmware V1 4 20 05 2021 70 113 7 1 Connections for 230 V AC top Basic Module SIOX Extension Module...
Страница 78: ...Firmware V1 4 20 05 2021 78 113 7 2 Connections for Protective Extra Low Voltage bottom...
Страница 84: ...Firmware V1 4 20 05 2021 84 113 7 3 Connections for Interfaces on the side Basic Module SIOX Extension Module...
Страница 103: ...Firmware V1 4 20 05 2021 103 113...