Firmware V1.4
20.05.2021
27/113
1.
2.
Setpoint flow
LT
This setpoint is used at two different places.
Note:
Observe the maximum flow temperature, see "Maximum flow temperature" above.
For monitoring the flow temperature in the LT water circuit and, if necessary, shutting down
the internal power signal.
Setpoint for internal power calculation
20..80
°C
35 °C
min water
pressure **
Minimum water pressure for monitoring the water circuit.
0..5 bar
1.2 bar
Alarm delay
water **
Delay until the alarm signalling of falling below the minimum water pressure.
0..3600
min
5 min
min. spread
CO
2
**
Minimum spread between CO
2
inlet temperature and outlet temperature.
5..90 K
5 K
Delay no
heating
power **
Delay until alarm signalling of no heating power available.
0..120
min
10 min
* The name of the parameter appears as a tooltip when the mouse is dragged over the setpoint.
** Parameter applies to heat recovery HT and LT.