Firmware V1.4
20.05.2021
102/113
•
•
•
•
The "standstill time" parameter specifies how long the air-conditioning function remains disabled. The
remaining time is displayed immediately below. The time runs from the time the air conditioning function is
deactivated.
A new setpoint for the GCBP is enabled with the "PV suction gas superheat" button.
Button to indicate whether a pressure transmitter is installed in the water circuit.
Button for activation of the common water circuit subfunction.
9.5 Visualisation in LDSWin - Service Area
The visualisation page “service area" is divided into two areas.
Upper range - sensor calibration
Overview of all Pt1000 temperature sensors with terminal number, current actual value (measured value) and a
brief description of the function. In addition, it is possible to calibrate each sensor individually in order to
compensate for any measurement errors that may occur due to very long connection cables by means of an
offset, for details see
Calibration of the Pt1000 Temperature Sensors
Lower area - service mode (password protected)
For test and service purposes, all analogue inputs and outputs of the controller can be manually overridden in
manual mode. The service mode is password protected and is only visible
after
entering a password, for details
Содержание WRG 3010 E
Страница 70: ...Firmware V1 4 20 05 2021 70 113 7 1 Connections for 230 V AC top Basic Module SIOX Extension Module...
Страница 78: ...Firmware V1 4 20 05 2021 78 113 7 2 Connections for Protective Extra Low Voltage bottom...
Страница 84: ...Firmware V1 4 20 05 2021 84 113 7 3 Connections for Interfaces on the side Basic Module SIOX Extension Module...
Страница 103: ...Firmware V1 4 20 05 2021 103 113...