5.7.1 Control Algorithm for MP Control
The medium pressure measured via an A/D converter is compared with the setpoint.
The input signal for the MP control valve is calculated using a PI controller. The amplification factors for the P-
component (parameter
p-factor
, menu 3-2-3) and the I-component (parameter
i-factor
, menu 3-2-3) can be
adjusted.
The correcting variable for the opening degree of the medium pressure valve can be limited with the
parameters
Min contr val.
and
Max. Con.Var.
(menu 3-2-3). The specification is entered as a percentage. If
Min
contr val.
= 0% and
Max. Con.Var.
=100%, the correcting variable of the MP controller will not be limited.
If the "Schnellrücklauf-Extern AUS" digital input (terminals 84, 85) has been activated and all compressors have
been unloaded, the analogue output is set to 0 volts. The MP control valve can also be operated in manual
mode. Using the parameter
Man. op. xxx %
in menu 3-2-3 MP Regulation, the valve opening degree can be set
from 0...100%. If "---" is entered, the opening degree is determined using the PI controller.
Manual mode is reserved for test and service purposes and is not stored in the controller memory, i.e. after a
power failure, controlled operation is active again. Manual operation cannot be activated via LDSWin.
5.7.2 Maintaining the MP by Limiting the HP-Valve
Depending on the medium pressure, the opening degree 0..100% of the HP valve is limited both downwards
and upwards. The limitation is performed as shown in the following graph:
Parameters
Menu
Parameter
Description
Input
Defa
ult
Dim.
3-2-3
MP Min
Lower limit for MP, HPV will be opened when Medium Pressure is lower
10...60
32
bar
3-2-3
dPm HP-V.Open
P-range for forced opening of the HPV in the case of undercutting the
minimum medium pressure setpoint
0..20
3
bar
However, these parameters should only be adjusted by trained specialist personnel!
Since all pressure transmitters measure absolute pressure values, the mean pressure setpoint
MP
setpoint
must also be parameterised as absolute pressure and not relative to the ambient pressure.
No MP regulation can take place in the event of failure of the MP pressure transmitter. A configurable
emergency opening degree (parameter
Stellsig.Not
, menu 3-2-3) is then output.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...