5.6.3 Temperature Sensors for the Regulation
There are two Pt1000 temperature sensors for the regulation of the gas cooler outlet temperature that are
recorded in the measuring range of -50 °C to +50 °C
t
gk1
(terminals 31/32) and
t
gk2
(terminals 29/30)
It must be differentiated here where these are located in the refrigeration pack system and what these are used
for.
The control sensor for the gas cooler is t
gk2
. If this shows any measuring circuit error, t
gk1
is switched to.
Position of the gas cooler outlet sensor with gas cooler bypass valve
If the gas cooler of the refrigeration pack system can be bypassed using a gas cooler bypass valve (3-way
valve), the gas cooler temperature sensors t
gk1
and t
gk2
are positioned at different locations.
t
gk2
is located directly after the gas cooler
t
gk1
is located directly after the gas cooler bypass valve
See following diagram.
If the gas cooler bypass valve is not active or not present, both temperature sensors usually show the same
value. They are redundant.
Incorrect positioning of the two gas cooler outlet sensors can result in high impairments of the
regulation of the gas cooler outlet temperature
and
calculation of the HP setpoint
. Always pay attention
to the correct position of the two gas cooler outlet sensors when using the gas cooler bypass valve.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...