13 Technical Data VS 3015 CT / SIOX
13.1 Electrical Data VS 3015 CT / SIOX
Basic module
SIOX extension module
Operating voltage
230 V AC, 200 ... 265 V AC, 50/60 Hz
24 V DC / 9 V DC
supply via basic module
Rated power
24 VA
3.1 W
Leakage current over PE
(protective earth)
max 1 mA
Digital inputs
24 x 230 V AC, floating
12 x 230 V AC, floating
Relay outputs
10 x 230 V AC, max. 6 A / min. 10 mA (6 NO
contacts, 4 changeover contacts), floating
8 x 230 V AC / max. 6 A / min. 10 mA
(4 x NO contacts, 4 x changeover contacts)
floating
Manual control switch
The pack controller as well as the extension modules have manual control switches
so that the regulation can be manually overridden in emergency operation, see chapter
operation manual-automatic mode selection
Analogue inputs 1)
13 x Pt1000 2-wire temperature sensor
2 x Pt1000 4-wire temperature sensor
6 x 4..20 mA (resistance 400 ohm)
1 x 0..10 V
-
Analogue outputs 1)
4 x 0..10 V / 4..20 mA
0..10 V (load min. 1 kΩ) / 4..20 mA (resistance max.
800 ohm)
-
1) Supply cables to analogue inputs / outputs must be shielded.
Basic module
SIOX extension module
Field bus interface
CAN bus, zero potential
-
Data interfaces
1x data interface for SIOX
Internal interface to basic module
2x serial RS232/RS485
1 x TTY (passive)
-
Archive memory
Compressor run times, switching pulses,
quotas, messages
-
Real-time clock
With power reserve, lithium cell
Type CRC 2450 N / 3 V Lithium
Battery life 10 years
Accuracy typically 12 minutes / year at 25 °C
-
Monitoring function
Watchdog
Other interfaces
Power supply for external SIOX
DANGER
Overvoltage category III / contamination degree 2:
All connections of the device provided for operation with 230 V AC supply voltage
must
be wired with
the same phase conductor. 400 V AC between neighbouring connection terminals is
not
permitted!
Overvoltage category II / contamination degree 2
or
overvoltage category II / contamination degree 1:
Different phase conductors may be used. 400 V AC between neighbouring connection terminals is
permitted!
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...