Firmware V1.41 V1
08.11.2022
113/219
6 VS 3015 CT Installation and Start-Up
The system centre, the operator terminal and the PC software LDSWin are used for the configuration of the
controller for the start-up and for later changes.
Furthermore, actual values and archived long-term data can be displayed. Basic hardware and software
settings must be made on the pack controller before the start-up of the system.
6.1 DIN Rail Mounting
The pack controller is available as version for DIN rail mounting. It is snapped on / fastened to the DIN rail using
two claws (on the underside of the device). The power loss of the device is 24 VA. This must be taken into
account for the installation. The pack controller can be put into operation after completion of the mechanical
and electrical installation.
6.2 Default hardware settings
The default settings of the pack controller are configured using the DIP switch S1, the decade switch S2 and
the jumper J1. The setting elements S1, S2 and J1 are located next to the cover on the PCB of the pack
controller (see picture).
DANGER
Important safety instructions!
Before the installation and start-up of the controller, the complete
must be read carefully and all safety instructions and hazard warnings must
be observed. Any maintenance by the user is not intended as possible hazards from incorrect re-
assembly cannot be ruled out. Opening the device is not authorised! Furthermore, it must be noted that
the safety of the system or the installation in which the device is integrated is the responsibility of the
creator of the system or installation. If the device is used in any way not specified by Eckelmann AG,
the protection supported by the device can be compromised!
The controller should only be used with compatible versions of the PC software LDSWin, otherwise the
scope of functions can be restricted.
Tip
: The
ATTENTION
The pack controller may only be mounted on a DIN rail and operated as an integrated regulation and
control device (EN60730). All supply lines from and to the device (with the exception of the 230 V
power supply and signal lines) must be shielded! This particularly applies for the analogue inputs
(sensor supply lines) as well as for the CAN bus cabling (cable type: LiYCY (TP)). These must also be
installed with sufficiently large distance from live cables. This prevents faulty measurements and
protects the device against electrical interference via the analogue inputs.
Protection type and dimensions can be found in the chapter
Technical Data VS 3015 CT / SIOX
.
DANGER
Warning about dangerous electrical voltage! Danger of electric shock! BEFORE
connecting and
disconnecting, it must be ensured that
no voltage
is present at all connections of the controller.
Wiring of the digital inputs:
All digital inputs of the pack controller must be set to 230 V AC for the
operation.
If 230 V AC is applied to an input that has been configured for 24 V AC, this results in destruction of the
control component.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...