It can be established with the alarm whether
the controller is correctly configured for the high pressure regulation. For example, the max. input signal of
the HP valve has been configured incorrectly.
there is any basic problem in the system. For example: the HP valve in the system has a defect.
The alarm delay is reset
during fast unload (active digital input 16)
during standstill of all compressors
during a restart (de-energised state) of the controller
Configuration of the monitoring
Parameter
Description
Input
Default
Dim.
Menu
Max HP Con.Err.
Maximum permissible control error in the
HP circuit. The function is deactivated with
input of "--".
0...30, --
5
bar
3-2-2-2
Del. MaxHP C.Er
Delay time, after which a fault message is
generated in the case of exceeding the
maximum permissible control error in the
HP circuit
0...100
15
min
3-2-2-2
The message has no influence on the control and regulation processes!
5.12.5 Monitoring of the Medium Pressure
5.12.5.1 Medium Pressure Monitoring Too High
The parameters required for the monitoring of the medium pressure can be configured using the menu 3-3. The
parameter
MP Off Comp xxx
sets the maximum permissible medium pressure. The message
MP too high
is
output if the pressure exceeds the specified limit value. The parameter
Nr.Comp.MP-Al x
defines the maximum
number of compressors that may be loaded in the event of any medium pressure fault. In the event of
exceeding
MP Off Comp
, there is an immediate step down to the specified number of compressors (no return).
If the parameter
Nr.Comp.MP-Al is set to "–", only a fault signal is generated without switching off the
compressor.
The
MP too high
signal is sent. The parameter
MD EIN xxx
b specifies the pressure for which the
compressor disabled by
MP Off Comp
is enabled again and the fault signal
MP too high
is reset. Compressor
activation after previous compressor disable due to an MP fault is performed after expiry of the configured lead
times.
5.12.5.2 Medium Pressure Monitoring Too Low
The system medium pressure should be in a specific range during normal operation of the system. In addition
to the medium pressure too high monitoring, the medium pressure is also monitored for undershooting a lower
limit value:
In the event of undershooting
MP too low
, the signal
MP too low
is output after expiry of a configurable signal
delay time using the parameter
Del. HP too l.
(menu 3-3). The signal is transmitted according to priority
preselection. This signal is not output in the case of measuring circuit errors of the MP transmitter. The
MP too
low
signal has no effects on the control and regulation processes.
5.12.5.3 Monitoring of the MP Control Error
If the medium pressure is different for longer than the configurable delay time minutes using the setpoint
Del.
MaxMP C.Er
by more than the configurable pressure setpoint using the setpoint
MP dif.
, the controller sends
the message
Deviation MP
(default priority 2).
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...