Firmware V1.41 V1
08.11.2022
91/219
•
•
•
•
•
•
•
•
Men
u
Parameter
Description
Input
Defau
lt
Dim.
FU-Rampe
V/s
Ramp for the actuating signal of the frequency converter
Example:
With a parameter setting of 1, the rate of change of the FC actuating signal is 0.1 V/
s
Attention!
The set value is reduced by a factor of 10!
0.1..5,0 1,0
V/s
5.10.2 LT compressor switching and standstill times
There are basic and variable switching times for the loading and unloading of the up to three LT compressors.
The variable times are calculated based on the configurable control constant.
A configurable Standzeit S1 is maintained for compressor 1 with the frequency converter.
Menu
Parameter
Description
Input
Default
Dim.
3-2-6
Basisz.LeiStu. ON →
Display basic times t
b
ON
→
Vari.Z.LeiStu. ON →
Display of the variable times t
v
ON
→
Basisz.LeiStu. OFF →
Display basic times t
b
OFF
→
Vari.Z.LeiStu. OFF →
Display of the variable times t
v
OFF
→
Regelkonstante XX K
Max. control error for variable switching times
1..15
2
K
Standzeit S1
Minimum standstill time of the LT compressor with FC after
shutdown
10..360
120
sec.
5.10.3 LT compressor monitoring
The following monitoring functions are applicable for the LT circuit.
Suction gas superheat
The superheat in the LT circuit is monitored and alarms are signalled if necessary.
The associated messages are:
Low superheat
Measuring circuit error
Cylinder head temperature
Cylinder head temperatures are monitored and alarms are signalled if necessary. Compressors are
unloaded or also disabled. The cylinder head temperature sensors are distributed among NT, MP and
LT compressors; a maximum of 8 sensors is possible.
The associated messages are:
High temp.
Measuring circuit error
Safety chain
The safety chain consists of:
LP cutout
Oil / HP switch (optional)
Motor overload cutout (optional)
An HP cutout for the LT circuit is
not
installed. However, the LT compressors are switched off
with the HP cutout of the NT circuit => no mechanical shutdown is performed
The LT compressor combined control does not have a neutral zone.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...