Firmware V1.41 V1
08.11.2022
86/219
No.
Parameter
Menu
Entry
Default
Dim.
Description
10
HD-Max.WRG
3-2-2-3
70...120
90
bar
Maximum HP setpoint in HRC mode. The parameter
is used for the shift via the analogue input. Max. limit
value for the HP setpoint that is transmitted via the
CAN bus.
Attention:
This parameter sets an upper limit on the
HP setpoint transmitted via the CAN bus.
11
HD-Min.WRG
3-2-2-3
50...120
75
bar
Minimum HP setpoint in HRC mode. The parameter is
used for the shift via the analogue input. Min. limit
value for the HP setpoint that is transmitted via the
CAN bus.
Attention:
This parameter sets a lower limit on the HP
setpoint transmitted via the CAN bus.
12
to-Schieb.WRG
3-2-2-3
OFF / outdoor
temperature /
CAN BUS
OFF
-
With this parameter, the to-setpoint can be shifted
above the temperature outside in HR mode and is
provided for the active heat pump operation that is
realised using a GLT 3010. When heat pump
operation is active, the request to shift to above
temperature outside is transmitted to the controller via
the CAN bus.
Attention!
The configured to-shift in menu 3-2-1-2 is
inactive during this time.
The to-shift in HR mode can either be deactivated or
parametrised via temperature outside or via CAN bus.
A physical value that is limited to a value between "
to-
Min.
" and "
to-Max.
" when received is transmitted via
the CAN bus.
13
to-Min.
3-2-2-3
-50...10, --
---
°C
Minimum value for the to setpoint shift via temperature
outside or CAN bus in HR mode. The parameter is
visible if the parameter "
to-Schieb.WRG
" is configured
to "YES" (version V5.37 and higher configured to
"
Aussentemp.
" or "
CAN-BUS
"). The to shift is inactive
in HR mode if set to "--".
14
ta-Min.
3-2-2-3
-25...20
0
°C
Minimum value of the temperature outside for which to
corresponds to the value of "
to-Min.
". The parameter
is visible if the parameter "
to-Schieb.WRG
" is
configured to "YES".
15
to-Max.
3-2-2-3
-50...10, --
---
°C
Maximum value for the to setpoint shift via
temperature outside or CAN bus in HR mode. The
parameter is visible if the parameter "
to-Schieb.WRG
"
is configured to "YES" (version V5.37 and higher
configured to "Aussentemp." or "
CAN-BUS
"). The to
shift is inactive in HR mode if set to "--".
16
ta-Max.
3-2-2-3
-18...35
20
°C
Maximum value of the temperature outside for which
to corresponds to the value of "
to-Max.
". The
parameter is visible if the parameter "
to-Schieb.WRG
"
is configured to "YES".
17
to-Rampe K/Min
3-2-1-2
1...20, --
---
K / Min
The to setpoint shift can be subjected to a ramp. The
ramp is inactive for "--". For to shift via analogue input
6 or via the CAN bus, a ramp speed of 1 K/min. is
active.
18
tg-Rampe K/Min
3-2-2-2
1...20, --
---
K / Min
The tg setpoint shift can be subjected to a ramp. The
ramp is inactive for "--".
19
HD Rampe/m
3-2-2-2
0.1...6.0
4.0
bar /
Min
Ramp for the HP setpoint calculation
Note: A changeover to a rate of change of 6 bar/min is
performed if the HP setpoint change is greater than 3
bar.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...