The external signal for HP setpoint shift is measured here via the analogue input 6 (terminals 50/51/52):
If there are 0 volts between the terminals 51 (+) and 52 (- or earth), the HP setpoint entered using the
parameter
HP-Min.HRC
is used.
If there are 10 volts between the terminals 51 (+) and 52 (- or earth), the HP setpoint entered using the
parameter
HP-Max.HRC
is used.
t
G
setpoint
In HRC mode, the setpoint for the regulation of the gas cooler outlet temperature can
be specified as in normal operation or
a fixed setpoint (configurable) that is active in HRC mode can be specified.
t
0
setpoint
In HRC mode, the to-setpoint for the regulation of the low pressure can be specified as follows:
Outdoor temperature (HRC 3010 A required)
CAN bus (HRC 3010 A required)
For example, this specification can be necessary if any outdoor compressor is present in the
refrigeration pack system!