Firmware V1.41 V1
08.11.2022
77/219
•
•
•
•
•
5.7.3 Medium Pressure Compressor
The medium pressure can be regulated in the controller using so-called parallel compressors whose intake side
is connected to medium pressure. These compressors are referred to below as medium pressure compressors
(abbreviated as "MP compressor"). The following diagram shows the position of an MP compressor.
Advantages of the MP compressors
Instead of conveying the refrigerant via a medium pressure valve from the medium pressure side to the intake
side of the HP compressor, it is more energy-efficient with MP compressors to pump the refrigerant directly to
the HP side.
The following functions are described in the following chapters:
Requirements
Actuation of the MP compressors for regulation of the medium pressure
Monitoring of the MP compressors
Pin assignment
5.7.3.1 Requirements
The following requirements must be met to be able to control the MP compressors (parallel compressors):
The jumper J1 must be set to RS485