Firmware V1.41 V1
08.11.2022
69/219
•
•
speed controlled fans to mains power operation (see also
Start-up of speed-controlled condenser fans /
The following diagram shows the speed sequence for starting using the example of a system with five fans:
In the case of a negative control error, the speed of all loaded fans is reduced to the minimum speed + 20%.
If the gas cooler outlet temperature remains below the setpoint, fan stages are switched off at intervals.
Switching back from mains power operation to controlled operation is not performed until the t
G
setpoint has
been undercut.
Finally, the speed controller is disabled via the first fan output S1 of the controller when the speed has reduced
to 0. If a minimum speed > 0 of the speed controller has been input using the parameter
Min. Drehzahl
(menu
3-2-2-1), the speed is reduced after a configurable time (parameter
B. unlo T F1
menu 3-2-2-2-c) to 0 using a
ramp and the fan output S1 is switched off.
Enable fan stages (parameter
ENABL.COND
screen 3-1-e)
The enable of the fan stages is directly assigned to the fan relay stages. Using a disable of the fan stage 1, the
speed controller with the connected fans can thus be disabled. If the first stage is disabled, the fan controller
operates as a step controller with the steps 2 to n-1.
The following maximum numbers of stages can be disabled or enabled:
Fan control via relays, requiring one SIOX extension module: 3 fan stages
Fan Control via Modbus : 11 fan stages
The stage
No. cond. 1
cannot be programmed for operation by power supply. It is not displayed on the
operator terminal, the store computer and in the LDSWin PC software.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...