Firmware V1.41 V1
08.11.2022
67/219
In the case of a negative control error, the speed controller is disabled using the first fan output F1 of the
controller if the speed has reduced to 0. If a minimum speed > 0 of the speed controller is entered using the
Min. speed
parameter (menu 3-3-1), the speed is reduced to 0 using a ramp and the fan output F1 is switched
off after a configurable time (Basiszeit AUS Lüfter 1).
Inactive speed controller enable (for Min. Speed >0):
Function: power supply bridging when
tg-Max
and/or
tg-Max.WRG
is exceeded.
The mains power operation is activated if the pressure has reached a specified t
G
limit value (parameter
t
G
-Max / t
G
-Max.HRC.
menu 3-2-2-1). The power supply bridging is performed by activating the second output
stage of the controller and disabling the first output stage (Freigabe Drehzahlsteller). Using the second output
stage, a bypass can be activated which switches the speed controlled fans to mains power operation (see also