5.6.4 Neutral Zone Fan Control
Step control
There is no switching of the fan stages in a configurable neutral zone with step control. This neutral zone is
configurable (parameter
Neutr.zone F
, see menu 3-2-2-2). The neutral zone has no function for continuous
control (
speed control, stages combined control, parallel combined control
).
The neutral zone parameter (parameter
Neutr.zone F
, see menu 3-2-2-2) is only displayed when the fans are
controlled by a step controller.
Continuous control
When the combined control type of control is active (stages combined control or parallel combined control), the
neutral zone speed control (parameter
NZ speed con.
, see menu 3-2-2-2) affects the switching on and off of the
fixed-speed fans.
If the actual value of the fan controller is within the neutral zone speed regulation, no fixed-speed fan is
switched on or off.
The enable of the speed controller for the fans occurs when the actual value of the fan controller exceeds the
setpoint minus half of the neutral zone speed controller. The enable for the speed controller is withdrawn when
the setpoint has been undercut and the speed = Min. speed (starts with Min. speed + Offset).
The enable for the speed controller is withdrawn when the setpoint is undercut and the speed = Min. speed
(starts with Min. speed + Offset).
The neutral zone speed control parameter (parameter
NZ speed con.
, see menu 3-2-2-2) is only displayed
when the fan is continuously regulated.
5.6.5 Control Algorithm tG with Step Controller
The gas cooler outlet temperature measured via an A/D converter is compared with the setpoint. The following
applies:
In the case of positive control error and increasing gas cooler outlet temperature, the step switch switches
forward one stage. This means that an additional gas cooler capacity stage is enabled. In the case of negative
control error and reducing gas cooler outlet temperature, the step switch switches back one stage. This means
that a gas cooler capacity stage is disabled.
Gas cooler capacity stages are also disabled (provided this is selected via the parameter
Fan off w/comp
(menu 3-3-1)) when all compressors are switched off.
5.6.5.1 Switching Times for Fan Motors with Step Controller
If the gas cooler outlet temperature rises or falls to a value outside the neutral zone, the first gas cooler capacity
stage is immediately switched on or off.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...