Firmware V1.41 V1
08.11.2022
51/219
5.5.2.1 Loading and unloading behaviour of the ejectors
The ejectors are controlled every second. The way in which the ejectors are switched on and off depends on
the set operating mode.
1. Gas ejectors
Operating mode: Thresholds
In the "Thresholds" operating mode, the gas ejector stages are switched on and off when the control value of
the small high-pressure valve exceeds or falls below the threshold by the differential value (parameter "Switch
Delta"). When the ejector stages are switched, the parametrised delay time (parameter "Delay Gas-Ej.) is
waited for.
Number of gas ejectors: 3
ejectors have the same size: NO