Firmware V1.41 V1
08.11.2022
43/219
HP valve for all compressors OFF
If all compressors are unloaded (e.g. by the controller, due to fault in the safety chain or by the digital input
"
Fast Unload
"), the regulation of the high pressure using the HP valve can be deactivated. The parameter "
HPV
off w/comp
" must be set to "Y" for this. In this case, the control signal is set to the value of "
Min contr val.
".
Menu
Parameter
Description
Input
Default
Dim.
3-2-2-2
HPV off w/comp
Close HP valve when switching off the
last of the running compressors
Yes / No
No
-
HP valve in emergency operation
The operating state is defined as emergency operation by the pressure transmitter of the high pressure
showing a measuring circuit error. In this case, the control signal of the HP valve is set to the configured value
of the "
Emerg. Con.Var.
" parameter.
Menu
Parameter
Description
Input
Default
Dim.
3-2-2-2
Emerg. Con.Var.
Control signal for HP control valve in
emergency operation (in the case of high
pressure measuring circuit error)
0..100
40
%
HP valve in manual mode
In the service case, for example during the first start-up, the HP valve can be actuated manually. The parameter
"
Man. op.
" must be set between 0 and 100% to the desired value of the HP valve for this. If "--" has been
entered, the opening degree is controlled via the PI controller. Manual mode is reserved for test and service
purposes and is not stored in the controller memory (i.e. after a power failure, controlled operation is active
again).
Menu
Parameter
Description
Input
Default
Dim.
3-2-2-2
Man. op.
Manual setting of the HP control valve
("---" = automatic)
--, 0...100
--
%
5.5.1.1 Neutral Zone HP-Control
In order to prevent very high activity of the controller correcting variable for the HP valve, a neutral zone has
also been provided for the continuous regulation of the high pressure. If the high pressure is lower than the
calculated HP setpoint plus half the neutral zone and greater than the pressure setpoint minus half the neutral
zone, the correcting variable (0.10 to 10 volts) of the HP valve is not changed.
As soon as the HP actual value enters the neutral zone, the previously output analogue control value remains
the same.
If 0.0 bar is input as neutral zone HP (parameter
Neutr.Zone HP
, menu 3-2-2-2), this function is deactivated.
The PI controller for the HP valve regulation now acts directly on the servo motor for the high pressure valve.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...