Firmware V1.41 V1
08.11.2022
215/219
No.
Message text
Process fault alarm
179
External alarm
Speed controller
External alarm digital input is active
Speed controller / external alarm digital input is active and speed / combined control is
activated
180
Service Mode
Service mode has been activated
181
Comp/cond. unload
External unload
182
Load shed x
Compressor has been disabled by load shedding - load shedding input x is active
185
Low refrigerant
Refrigerant level switch tripped
186
Max. speed
Upper threshold value for speed controller exceeded
187
Manual OFF Sx
Toggle to Manual OFF - compressor stage Sx
LT Manual OFF Sx
Toggle to Manual OFF - LT compressor stage Sx
188
Manual ON Sx
Toggle to Manual ON - compressor stage Sx
LT Manual ON Sx
Toggle to Manual ON - LT compressor stage Sx
192
External fan
Currently not used
193
Emerg. working
Emergency operation / load shedding digital input 2 is active and emergency operation is
enabled
203
Sens. type change
A parameter for calibration of the pressure transmitters has been changed
204
Aut. lock Sx
Compressor stage x has been automatically locked (5x cylinder temperature too high per
day)
219
Meas. error MP
Error in the measuring circuit for measurement of the medium pressure
220
MeasErr.gas.out
Error in the measuring circuit for the gas cooler outlet temperature
MeasErr.gas.out2
Error in the measuring circuit for the gas cooler outlet temperature 2
221
High switching frequency
Switching frequency too high for compressor combined control
LT too many starts
Switching frequency too high for compressor combined control LT
222
No load level
No load level information received for t
0
shift via consumer
225
Measuring circuit error
Error in measuring circuit for suction gas temperature / superheat
231
Ext.to-shift
Error in measuring circuit for external t
0
shift
232
M.err.ext.HP-shift
Error in measuring circuit for external HP shift
233
High MP
Medium pressure too high
237
Deviation HP
High pressure control error too high
238
Deviation MP
Medium pressure control error too high
240
Setpoint change
A setpoint has been changed
247
Speed controller HP
Error in the speed controller during high pressure combined control
248
Max Akk. Level
The max. level in the accumulator has been exceeded
248
Oil-Shortage
Oil shortage in the pack
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...