Firmware V1.41 V1
08.11.2022
214/219
•
•
No.
Message text
Process fault alarm
142
Low Superheat
Minimum superheat undercut
Low Superheat LT
Minimum superheat LT undercut
150
Mot. cutout Cx
Compressor Cx motor overload cut-out tripped
Motor temp. LT x
LT compressor Cx motor overload cutout tripped
Mot.temp 1/FC-fault
Compressor 1 motor overload cutout tripped / frequency converter fault
Mot.temp 1/F.fau LT
Compressor 1 motor overload cutout tripped / frequency converter fault LT
153
Motor overload cutout fan x
Condenser fan x motor overload cut-out tripped
Comm.Error Fx
ebm-papst fan
no
ebm-papst fan available or
at least one switching order of an
ebm-papst fan
is configured as "–"
Comm.Error F1..12
Fault in the Modbus communication with an ebm-papst fan (1..12)
EBM Manual Run
Manual adjustment of the ebm-papst fan speed
154
Oil diff. pr. Cx
HP-Fault Cx
Oil/HP-Fault Cx
Compressor Cx low oil pressure switch or
Compressor Cx HP monitor or
Compressor Cx combination HP/oil monitoring tripped
Menu 3-1: Message text according to selection via parameters:
Oil.diff.pr Cx, HP-Fault Cx or Oil/HP-Fault Cx
Oil/HP fault LT x
LT Compressor Cx combination HP/oil monitoring tripped
157
High Cyl.temp. Cx
Cylinder head temperature for compressor Cx upper limit value exceeded
High Cyl.temp LT x
Cylinder head temperature for LT compressor Cx upper limit value exceeded
160
HP cutout
High pressure limiter tripped
161
LP cutout
Low pressure cutout tripped
LP limiter LT
LT low-pressure cutout tripped
163
M.err.Suctiongas LT
Error in the measuring circuit for measurement of the suction gas superheat
164
Low LP
Lower limit value t
0
undercut
t
0
too low LT
Lower threshold LT t
0
undercut
167
High HP
HP upper limit value exceeded
168
Meas.err.cyl. Cx
Error in the measuring circuit for measurement of the compressor x cylinder head
temperature
Meas.err.cyl. LT
Error in the measuring circuit for measurement of the LT compressor x cylinder head
temperature
171
Meas. error HP
Error in the measuring circuit for measurement of the high pressure
172
Meas. error LP
Error in the measuring circuit for measurement of the low pressure
173
Meas. err. LP Z2
Error in the measuring circuit for measurement of the Z2 low pressure
175
Meas. error outdoor temp.
Error in the measuring circuit for measurement of the temperature outside
176
Meas. error tr
Error in the measuring circuit for measurement of the room temperature
177
Meas. error Humidity
Error in the measuring circuit for measurement of the air humidity
178
Burst disk
Burst disk digital input tripped
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...