Firmware V1.41 V1
08.11.2022
197/219
LT-REFR. ID: XXXXX
Description
Input
Default
Dim.
Enable LT contr.
Activation of the LT compressors control
Y/N
Y
-
No. comps.
Number of LT compressors
1..3
3
-
Enable comp.stages
Enable of the individual capacity stages
-
-
-
Mot.cutout comp
Enable for the motor protection monitoring of the LT
compressors
Y/N
N
-
Oil/HP-Switch
Enable for the oil/HP monitoring of the LT compressors
Y/N
N
-
to shift
t
0
shift via consumer
ON/OFF
OFF
-
to Max. Day
max. t
0
setpoint for setpoint shift during the day (only
visible when t
0
shift is ON)
-50..-16
-34
°C
to Min. Day
min. t
0
setpoint for setpoint shift during the day (only
visible when t
0
shift is ON)
-50..-16
-38
°C
to Max. Night
max. t
0
t
0
setpoint for setpoint shift during the night (only
visible when t
0
shift is ON)
-50..-16
-34
°C
to Min. Night
min. t
0
t
0
setpoint for setpoint shift during the night (only
visible when t
0
shift is ON)
-50..-16
-38
°C
to Setpt Day
t
0
setpoint daytime operation
-50..-16
-38
°C
to Setpt Night
t
0
setpoint night operation
-50..-16
-38
°C
Basic unload time ON
Display basic times t
b
ON
→
Vari.Z.LeiStu. ON
Display of the variable times t
v
ON
→
Basic unload time OFF
Display basic times t
b
OFF
→
Vari.Z.LeiStu. OFF
Display of the variable times t
v
OFF
→
Off Time S1
Minimum standstill time of the LT FC compressor after
shutdown
10..360
120
sec.
p-factor X.X
p-factor of the combined control for the Z2 compressors
Example: for control error of 1 K with a p-factor of 1, the p-
component is 1 V
0.0..3.0
0.7
V/K
I-Wert X.XX
i-factor of the combined control for the Z2 compressors
Example: for control error of 1 K with an i-factor of 0.5, the
i-component changes with 0.05 V per cycle time (1
second) of the controller
Attention: The set value is reduced by a factor of 10!
0.00..1.00
0.10
V/K. s
Control const. XX K
Max. control error for variable switching times
1..15
2
K
FC ramp V/s
Ramp for the control signal of the frequency converter
0.1..5.0
1.0
V / s
Min.Superheat
Threshold for the monitoring of the minimum superheat
2.0..15.0
4.0
K
Del.Min.OH
Delay time for the monitoring of the minimum superheat
0..15
1
m
Cyl.Head Alarm
Threshold for the monitoring of the cylinder head
temperature
70..160
130
°C
Cyl.Head Del.
Delay time for the monitoring of the cylinder head
temperature
0..5
3
m
t
0
Comp OFF
LT t
0
lower limit for compressor shutdown
-58..-2
-46
°C
Del. t
0
OFF
Delay for "t
0
too low LT" alarm
0..60
10
m
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...