Firmware V1.41 V1
08.11.2022
195/219
•
•
•
MP-CONT ID: XXXXX
Description
Input
Default
Dim.
dPm HDV ZU Xb
P-range for forced closing of the HPV in the
case of exceeding the maximum medium
pressure setpoint
0..20,--
2
b
dPm HDV AUF Xb
P-range for forced opening of the HPV in the
case of undercutting the minimum medium
pressure setpoint
0..20,--
3
b
Min.Stellsig. XX%
Minimum control signal for the MP control valve 0..100
0
%
Max.Stellsig. XX%
Maximum control signal for the MP control
valve
0..100
100
%
Stellsig.Not XX%
MPV control signal for MP control valve in
emergency operation (tg or MP measuring
circuit error)
0..100
40
%
Max.Regabw.MD Xb
Maximum permissible control error in the MP
circuit. The function is deactivated with input of
"--".
0..30
5
b
VzgMax.Rabw. Xm
Delay time, after which a fault message is
generated in the case of exceeding the
maximum permissible control error in the MP
circuit.
0..100
15
min
Screen 3-2-4 Spray System
SPRAY ID: XXXXX
Description
Input
Default
Dim.
Spray-System X
Activation of spray system Y/N
Y/N
N
-
Nachtbetrieb X
Spray system active in night operation Y/N
Y/N
N
-
Temp. S1 Min. XX °C
Gas cooler outlet temperature at which stage
1 of the spray system is switched on
20..40
32
°C
Min. EIN S1 XX m
Minimum run time for stage 1 of the spray
system
30..180
60
minutes
Tempdif.S2 EIN X K
Temperature difference above switch-on
temperature for stage 1 at which stage 2 is
switched on
2..10
2
K
Hysterese XX K
Temperature difference below switch-on
temperature for stage 1 at which stage 1 is
switched off again
7..10
7
K
Menu 3-2-5 MD-Verbund-Reg (menu only visible if parallel compressors have been configured in menu 3-1
Configuration)
MP PACK ID: XXXXX
1 Control
Continue to menu 3-2-5-1
2 MP control
Continue to menu 3-2-5-2
Menu 3-2-5-1 Compressor control MP pack
MP PACK ID: XXXXX
Description
Input
Default
Dim.
Type of control →
Selection of the control type for the MP pack
Y/N
N
-
p-factor X.X
p-factor of the PI controller
Example: for control error of 1 K with a p-factor of
1, the p-component is 1 V (unit V/K)
0.0..3.0
0.7
-
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...