Firmware V1.41 V1
08.11.2022
193/219
•
•
Screen 3-2-2-3-b to-adjustment HR
HR to Shift ID:XXXXX
Description
Input
Default
OFF
to-adjustment is off
√
√
Outdoor temp.
to-adjustment via temperature outside
CAN bus
to-adjustment via CAN bus
Screen 3-2-2-4 Ejectors
EJECTORS ID:XXXXX
Description
Input
Default
Dim.
Use Gas-Ej.
Gas ejector operation
YES / NO
YES
-
Operation Mode
Mode of the gas ejector operation:
0 → Thresholds: using thresholds of the small high
pressure valve and unknown ejector sizes
1 → Ejector size: using global opening degree and
parametrisation of the ejector sizes and the small high
pressure valve
→
Screen 3-2-2-4-
a
-
No. Gas Ejectors
Number of gas ejectors
1..8
6
-
Ejector Sizes
Sizes of the gas ejectors
(only visible in the "Ejector Sizes" operating mode")
→
Screen 3-2-2-4-
b
Size HPV
Size of the small HP valve
0..100
100
%
Ej. Equal Sized
Equal size ejectors
(only visible in the "Thresholds") operating mode
YES / NO
NO
-
Threshold On
Max. threshold of the small HP valve for switching on
the next largest ejector stage
(only visible in the "Thresholds") operating mode
0..100
70
%
Threshold Off
Min. threshold of the small HP valve for switching on
the previous smaller ejector stage
(only visible in the "Thresholds" operating mode)
0..100
30
%
Delay Gas-Ej.
Basic delay time for the switching of the gas ejector
stages
0..250
30
s
Switch Delta
Switch Delta for exceeding the limit for switching the
ejector stages
0..10
0
%
Switch Slope
Ramp speed for the switching process from large HP
valve to small HP valve in ejector operation in volts per
second
In the case of parametrisation to 5, the ramp speed is
0.5 V/s.
The ramp can be deactivated by setting this parameter
to --.
0.1..5.0
5.0
V/s
Use Fl-Ej.
Liquid ejector operation
YES / NO
YES
-
Acc. Level Ctrl
Liquid ejector control according to
YES → accumulator level
NO → high pressure with priority according to
temperature outside
YES / NO
YES
-
No. Fl-Ej.
Number of liquid ejectors
0..3
2
-
No. Acc.Sens.
Number of accumulator fill level switches
2..4
3
-
Delay FlEj.
Delay time for the switching of the liquid ejector stages
0..250
30
s
Waiting Time LE ON
Delay time for loading another liquid ejector stage
0..250
120
s
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...