Firmware V1.41 V1
08.11.2022
192/219
•
HR ID: XXXXX
Description
Input
Default
Dim.
tG Anheb.WRG
Parameter to use a fixed tg-setpoint in HR
mode. This value can be configured with the
"
tG-Setp. WRG
" parameter.
Y/N
N
tG-Soll WRG
tg setpoint for the HR mode (only visible if "
tG
Incr.WRG
" = Y)
0..30
0
°C
Lü. AUS im WRG
Activates the fan shutdown in HR mode. If the
parameter "HR mode" is configured to "CAN-
BUS" and the "Switch off fans" request arrives
via the CAN bus, the fans in HR mode are
switched off.
Y/N
N
Off.ext.Sig X%
Offset for HR setpoint shift (only visible if
parameter "
Setp.shift.
" is configured to "YES")
0..25
0
%
HD-Max.WRG XXb
Maximum high pressure in HRC operation
70..120
90
b
HD-Min.WRG XXb
Minimum high pressure in HRC operation
50..120
75
b
to-Schieb.WRG
Setting of the to-adjustment for the HR mode.
The to-adjustment in HR mode can either be
deactivated or parametrised via temperature
outside or via CAN bus. A physical value that is
limited to a value between "
to-min.
" and "
to-
max.
" when received is transmitted via the
CAN bus.
→
Screen 3-2-2-3-b
to-Min.
Minimum value for the to setpoint shift via
temperature outside or CAN bus in HR mode.
The parameter is visible if the parameter "
to-
shift HR
" is configured to "
Outdoor temp.
" or
"
CAN-BUS
". The to-adjustment is inactive in
HR mode if set to "--".
-50..10, --
---
°C
ta-Min.
Minimum value of the temperature outside for
which to corresponds to the value of "
to-Min.
".
The parameter is visible if the parameter "
to
shift HR
" is configured to "temperature
outside".
-25..20
0
°C
to-Max.
Maximum value for the to setpoint shift via
temperature outside or CAN bus in HR mode.
The parameter is visible if the parameter "
to-
shift HR
" is configured to "
Outdoor temp.
" or
"
CAN-BUS
". The to-adjustment is inactive in
HR mode if set to "--".
-50..10, --
---
°C
ta-Max.
Maximum value of the temperature outside for
which to corresponds to the value of "
to-Min.
".
The parameter is visible if the parameter "
to
shift HR
" is configured to "temperature
outside".
-18..35
20
°C
Gasc.speed.HP XX%
Speed specification in HR mode when the heat
pump is active means the gas cooler is 100%
bypassed. For "--", this function is not active
0..100, --
---
%
Screen 3-2-2-3-a HR mode
HR MODE ID:XXXXX
Description
Input
Default
Digital input
Activation of the HR mode via digital input
√
√
CAN BUS
Activation of the HR mode via CAN bus
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...