Firmware V1.41 V1
08.11.2022
187/219
•
•
HP CONT ID: XXXXX
Description
Input
Default
Dim.
Timeb.I-fact. XX s
Time interval for calculation of i-component for fan speed control signal
(only visible if speed controller or combined control type of control has been
selected - screen 3-2-2-1-a)
1..60
10
s
Offset XX%
Offset for fan speed correcting variable
(only visible if the speed controller or combined control type of control has been
selected - screen 3-2-2-1-a)
1..50
10
%
Switch mode
→
Fan control / star-delta operation switch mode
(only visible if step controller type of control has been selected - screen 3-2-2-1-
a)
→
Screen
3-2-2-1-d
Fast speed N X
Fast speed (delta operation) also permitted for night setpoint Y/N
(only visible if step controller type of control (screen 3-2-2-1-a) has been selected
and parameter
Switch mode
SSFF or SSSF has been selected (screen 3-2-2-1-
b)
Y/N
Y
-
Del. slow speed XX s
Delay of loading a fan stage in star operation after it has been unloaded from
delta operation
(only visible if
step controller
type of control (screen 3-2-2-1-a) has been selected
and
Switch mode
SSFF or SSSF has been selected (screen 3-2-2-1-b)
0..30
5
s
tG-Max XX°C
Max. gas cooler outlet temperature for switching to power supply bridging
---, 25..56 28
-
-
Fan off w/comp X
Switch off fans with compressors YES/NO
Y/N
N
-
Fan X OFF by al. X
Switch off fans when motor overload cutout is tripped YES/NO
Y/N
Y
-
Fan Kickstart X
For activating the kickstart function for the fans
Y/N
N
Fan Offtime
Standstill time of a fan, after which a kickstart is performed (only visible if
parameter
Fan Kickstart
is set to YES).
24..240
24
h
Fan Kicklimit
tc-Setpoint / tc-Actual difference, from which the function will be active. For
example for tc-Setpoint = 20 °C,
Fan Kicklimit
= 5 K. Function would be active
starting from a tc-Actual greater than 15 °C
(only visible if the parameter "Fan Kickstart" is set to YES)
0..20
5
K
Fan Scan Repl. X
"Partial Search": only new fans added to the Modbus are searched for here, e.g.
in the case of replacement of a defective fan. (see
Condition: the new fan must have the Modbus address 1 (factory setting). If this
is not the case, the "Manual Search" (recommended) or the "Complete Search"
must be performed
Y/N
N
New SNo:
"Manual Search": an ebm-papst fan can be added by entering its serial number
(e.g.
1703000103
).
10-digit
number
Screen 3-2-2-1-a Type of control HP
CONTROL ID: XXXXX
Description
Input
Default
Dim.
Step controller √
Selection list of the HP type of control
√
√
-
Speed controller
-
Combi-cont.parall
-
Combi-cont.stages
-
Screen 3-2-2-1-b Switching order - Definition of the fan switching order
FAN.ORD. ID:
XXXXX
Description
Input
Default
Dim.
ssssssssss A:aa
X
Switching position of the fan with 10-digit serial number ssssssssss and Modbus
address aa
--, 0, 1..12
---
-
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...