Firmware V1.41 V1
08.11.2022
183/219
•
•
•
Menu 3-2-1-3 LP-Control day
LP CONT D ID: XXXXX
Description
Input
Default
Dim.
to-Max.XXX °C
Max. t
0
setpoint for setpoint shift
-50..10
-8
°C
tr-Min.XXX °C
Minimum room temperature for setpoint shift
(only visible if t
0
-adjustment via room
temperature - screen 3-2-2-a)
-25..20
15
°C
to-Min.XXX °C
Min. t
0
setpoint for setpoint shift
-50..10
-12
°C
tr-Max.XXX °C
Max. room temperature for setpoint shift (only
visible if t
0
-adjustment via room temperature -
screen 3-2-2-a)
-18..35
25
°C
humid. shift X
Humidity shift activated YES/NO
Y/N
N
-
Basic unload time ON
→
Display basic times t
b
ON
→
Screen 3-2-1-3-a
Vari. unload time ON
→
Display of the variable times t
v
ON
→
Screen 3-2-1-3-b
Basic unload time
→
Display basic times t
b
OFF
→
Screen 3-2-1-3-c
Vari. unload time
→
Display of the variable times t
v
OFF
→
Screen 3-2-1-3-d
Dead band XX K
Switching hysteresis for step control (only
visible for "step control" type of control)
1..10
4
K
NZ speed con. 0K
Dead band for the loading and unloading of
fixed-speed compressors during combined
control (only visible for "combined control" type
of control)
0..6
0
K
Control const. XX K
Max. control error for variable switching times
1..15
10
K
Screen 3-2-1-3-a Basic time capacity stage ON
B. LOAD T ID: XXXXX
Description
Input
Default
Dim.
B. LOAD T S1 XXX s
Only the available capacity stages are
displayed.
0..250
30
sec.
B. LOAD T S2 XXX s
3..250
60
sec.
B. LOAD T S3 XXX s
3..250
90
sec.
B. LOAD T S4 XXX s
3..250
120
sec.
B. LOAD T S5 XXX s
3..250
150
sec.
B. LOAD T S6 XXX s
3..250
180
sec.
..
B. LOAD T SN* XXX s
3..250
180
sec.
*Basic module: 1 – max. 4 capacity stages
with first SIOX extension module: 1 - max. 8 capacity stages
Screen 3-2-1-3-b Variable time capacity stage ON
V. LOAD T ID: XXXXX
Description
Input
Default
Dim.
V. LOAD T S1 XXX s
Only the available capacity stages are
displayed.
0..250
250
sec.
V. LOAD T S2 XXX s
3..250
250
sec.
..
V. LOAD T SN* XXX s
3..250
250
sec.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...