Firmware V1.41 V1
08.11.2022
177/219
CONFIG ID: XXXXX
Description
Input
Default
Dim.
Del.Oil/HP-F. xx m
Delay time for the messages from menu 3-1-c
0..10
0
min
Enable comp.stages
→
enable of the capacity stages
→
Screen 3-1-c
Emerg. working X
Emergency operation YES/NO
Y/N
N
-
No.emerg.stages X
Number of capacity stages for emergency operation
(only visible if Notbetrieb Y)
1..3/7
3/7
-
CompOFF.w.LdSh X
In the case of load shedding and system configuration
with capacity-controlled compressors, one complete
compressor (with capacity stages) per load shedding
stage is unloaded (only visible for system configuration
with capacity-controlled compressors: No.cap.stages >
1)
Y/N
N
-
Par. compr.
Parallel compressor
Y/N
N
No. par. compr. X
Entry of number of parallel compressors (only visible if
"Par. compr." Y)
1..4/8
0
-
No. PC with CC X
Entry of the number of parallel compressor with capacity
stages
0..6
0
-
No. CapStage/PC X
Entry of the number of capacity stages per parallel
compressor
1..3
1
-
PC delay oil/HP
Parallel compressor delay
0..10
0
min
PC enable stage
Enable parallel compressor capacity stage
→
Screen 3-1-d
Mot. prot. PC
Enable parallel compressor motor overload cutout YES/
NO
Y/N
N
-
Oil/HP cont. PC
Oil pressure difference switch / HP switch parallel
compressor YES/NO
Y/N
N
-
No. cond.stages X
Number of condenser stages
1..4/8/12
4/8/12
-
Enable cond.stages
→
Display of the condenser stages
→
Screen 3-1-e
Modbus relays
Display of the Modbus modules
→
Screen 3-1-f
Outdoor temp. XXX
Enable outdoor temperature sensor ON/OFF
ON/OFF
ON
-
Room temp. XXX
Enable room temperature sensor ON/OFF
ON/OFF
ON
-
Humidity X
Enable humidity sensor ON/OFF
ON/OFF
OFF
-
Node-No Env.dat XX
CAN bus address (node number) of the pack controller
of which the ambient data should be used.
1..9, –
–
-
Transmitter Z2 X
Pressure transmitter for Z2 available
Note: The parameter "Transmitter Z2" must be set to
YES so that the suction gas pressure of the LT
compressor is transmitted to the LT refrigeration points.
Y/N
Y
-
Sig. setp. toggle X
Toggle setpoint signal
0 = Low active
1 = High active
0/1
1
-
COP Sensor h1
→
Selection of the sensor for determining the h1 enthalpy
→
Screen 3-1-g
COP Sensor h2
→
Selection of the sensor for determining the h2 enthalpy
→
Screen 3-1-h
COP Sensor h3
→
Selection of the sensor for determining the h3 enthalpy
→
Screen 3-1-i
COP_HG_Offset X
Offset for the measured value of the h2 enthalpy of the
hot gas sensor in Kelvin
0..50
0
K
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...