Firmware V1.41 V1
08.11.2022
175/219
•
•
•
•
•
Basic module with first SIOX extension module: 1 - max. 4 fans
Basic module with ebm-papst fan via Modbus: 1 - max. 12 fans
*The fast speed is only possible up to stage 6 in the SSFF operating mode and up to stage 11 in the SSSF
operating mode.
Menu 2-4 System actual values
SYSTEMID: XXXXX
HP cutout XXX
HP cutout digital input
LP cutout XXX
LP cutout digital input
LT LP cutout XXX
LT LP cutout digital input
Burst disk XXX
Burst disk digital input (only visible if Refr. Max Mon is not active)
Max.level XXX
Maximum refrigerant level digital input (only visible if Refr. Max Mon is active)
Low liq. level XXX %
Refrigerant level monitoring
Setp. toggle XXX
Setpoint toggle digital input
Heat recovery XXX
Heat recovery digital input
Comp/cond. unload
XXX
Comp/cond. unload digital input
Load shed 1 XXX
Load shed 1 digital input
Cons.enab..CAN
XXX
Consumer enable via CAN bus
Cons.enab..Rel XXX
Consumer enable relay output
toggle Comp. XXX
Status of relay output for FC compressor base load rotation for compressor combined control (only visible if
compressor combined control is activated: parameter Control type on Combined Control menu 3-2-1-1-a)
Suc.gas injec. XXX
Compressed gas cooler / suction gas injector status relay output
HG-Dump XXX
Hot gas bypass function status relay output
Accum. Level 1 XXX
Accumulator state Level 1 status digital input
Accum. Level 2 XXX
Accumulator state Level 2 status digital input
Accum. Level 3 XXX
Accumulator state Level 3 status digital input
Oil-Shortage XXX
Oil shortage for ejector operation status digital input
Oil return XXX
Oil return for ejector operation status relay output
Menu 2-5 - Menu item is hidden
Menu 2-6 COP
COP ID: XXXXX
COP Cooling.X.XX
COP in cooling mode - updating only in cooling mode
COP WRG X.XX
COP in heat recovery mode - always the current value
COP efficien. X.XX
COP efficiency
Menu 2-7 Cond. mon.
Menu 2-8 Ejectors
The condenser monitoring function must be deactivated (menu 3-9a set to "Off")!
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...