ANALOGW.ID: XXXXX Display of the archived refrigeration point data in the store computer
Setp FC Fan XXX %
Currently output correcting variable in percent for fan speed (100% corresponds to 10 V at the analogue output)
Act. MP
↑
/
↓
/
↔
XXX b
Current medium pressure
Setp. MPXX b
Setpoint medium pressure for comparison
MP-Control XX %
Current opening degree of the medium pressure control valve
Cyl. Temp.
Analogue cylinder head temperature values, continue to screen 2-1-a
LT Cyl. Temp.
Analogue cylinder head temperatures LT circuit, continue to screen 2-1-b
hot-gas temp. XX°C
Hot gas temperature
Act. LP Z2 XXXb
Current low-pressure Z2
Setp. LP Z2 L/N XXXb
Low-pressure setpoint for comparison
Act. t0 Z2 XXX°C
Current low pressure temperature Z2
Setp. t0 Z2 L/N XXX°C
Low pressure temperature Z2 setpoint for comparison
Comp.Speed LT XX%
Z2 compressor speed
Suctiongas LT X.X°C
Current Z2 suction gas temperature
Superheat Z2 X.X K
Current superheat Z2
HR-setpoint X %
Analogue input for HR setpoint shift, only visible when setpoint shift is activated (menu 3-2-2-3)
Contr. EJCT
Control signal (global opening degree) for gas ejectors
Ej. HPV
Small HP vale opening degree in ejector operation
N = night operation
T = day operation
S = subcritical
T = transcritical
HR = heat recovery operation
Screen 2-1-a Cylinder head temperatures analogue values / Screen 2-1-b Cylinder head temperatures LT
ANALOGW.ID: XXXXX
Cyl. temp. C1 XX °C
Cylinder head temperature display for first compressor
...
Only the actual number of compressors is displayed*
Cyl. Temp. C8* XX °C
Cylinder head temperature display for eighth compressor*
*depending on the configuration and compressor type, the number of the displayed capacity stages is:
for NT and parallel compressors with basic module: 1 - max. 4
for LT and parallel compressors with first SIOX extension module: 1 - max. 8
for LT compressors: 1 - max. 3
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...