10.1.3 Menu 2 Actual values
ACT.VALUES ID:xxxxx
1 Analogue values
Continue to menu 2-1
2 Compressors
Continue to menu 2-2
3 Condenser fans
Continue to menu 2-3
4 System
Continue to menu 2-4
5
-
6 COP
Continue to menu 2-6
7 Cond. mon.
Continue to menu 2-7
8 Ejectors
Continue to menu 2-8
Menu 2-1 Analogue values
ANALOGW.ID: XXXXX Display of the archived refrigeration point data in the store computer
Act. LP +/-/= X.XX b
Current evaporating pressure
Setp.LP L/N X.XX b
Evaporation pressure setpoint for comparison
Act. to +/-/= XX °C
Current evaporating temperature
Setp. to L/N XX °C
Evaporation temperature setpoint for comparison
SuctGasTemp XX °C
Current suction gas temperature
Superheat XX K
Current suction gas superheat
Room temp. XX °C
Current room temperature
Humidity XXX %
Current humidity
Ext.to-shift XXX %
Current default for to-adjustment via external 0..10 V signal
Comp.Speed.XXX %
Currently transmitted control variable for compressor speed in percent (only visible when no min. and max. FC
frequencies are entered. 100% corresponds to 10 V at the analogue output).
Comp.Speed.OH
Currently transmitted control variable for compressor speed scaled in Hz (only visible when no min. and max.
FC frequencies are entered)
Act. HP ↑/↓/↔ S/T X.XX
b
Current high pressure
Setp. HP WR X.XX b
High pressure setpoint for comparison
Act. tc XX °C
Current condensation temperature (indicates -- in the transcritical range)
Outdoor temp. XX °C
Current temperature outside (option)
HP ctrl.valve XX %
Current opening degree of the high pressure control valve
OD HP-Valve.XX %
Current opening degree of the high pressure control valve, retrieved via analogue input 2 (only visible if
activated under HP Control)
Act. tG XX °C
Current gas cooler temperature
Act. tG2 XX °C
Current gas cooler temperature measured by the redundant tg2 sensor
Act. Ctrl.
↑
/
↓
/
↔
S/TXX
°C
Currently used actual value for the fan control (gas cooler outlet temperature tG or condensation temperature tc,
with trend indication)
Setp. tG HR XX °C
Gas cooler temperature setpoint for comparison (with indication of control or heat recovery setpoint)
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...