Firmware V1.41 V1
08.11.2022
158/219
•
•
8.2 Service Mode
After selection of the pack controller
Service Mode
(menu 8), all compressors and fan outputs are reset step by
step.
Then all controller functions are inactive so that each digital and analogue output can be set manually. The
controller registers the
Service Mode
by the entry of a message in the log memory. Transmission is performed
according to priority selection.
8.3 Display of the Operating States
Some rows of the display have additional symbols before the operating states of the system measured value.
The following additional symbols are displayed.
Display of the suction pressure trend:
Shows whether compressor capacity stages should be loaded, unloaded or not switched after expiry of the
delay times.
Display of the gas cooler outlet temperature trend:
Shows whether compressor capacity stages should be loaded, unloaded or not switched after expiry of the
delay times.
The operating modes "subcritical" and "transcritical" as well as the trend display are also shown for the
controller:
In the
service mode
the switching commands to the relays or the specifications to the analogue outputs
(voltage 0..10 V or current 4..20 mA) are performed immediately!
The digital and analogue inputs (motor overload cut-out, oil pressure difference switch, pressure
transmitter etc.) are not taken into account.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...