Firmware V1.41 V1
08.11.2022
152/219
Type
Photo
Function
Part number
Modbus analogue module
4 analogue outputs
0..10 V DC
MODBAOUT02
Power
supply
-
230 V AC /
24 V DC, 1.3 A
KGLNT24V1P
Connection of Modbus modules to the basic module and the power supply
Modbus modules can be connected to the RS485 interface of the basic module to increase the inputs / outputs.
e
Configuration of the Modbus modules
Terminal assignment of the Modbus analogue module
Terminal No.
Function (0..10 V)
No.
MR-AO4
1
1
C2
FC Medium pressure compressor
+0..10 V
GND
2
2
C2
FC Fan
+0..10 V
GND
* Note:
A terminating resistor of 100 Ohm
must
be installed at the end of the Modbus cable
(drawing on the left, part number KGLCANTERM).
The Modbus modules are set with
parity = even
and
bit rate of 19200 bit/s
at the factory. See
description of the Modbus modules for details.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...