Firmware V1.41 V1
08.11.2022
148/219
1
2
3
4
5
6
7
8
9, 10
11, 12
13, 14
15, 16
17, 18
19, 20
21, 22
23, 24
Cylinder head temperature C1
Cylinder head temperature C2
Cylinder head temperature C3
Cylinder head temperature C4
Cylinder head temperature C5
Cylinder head temperature C6
Cylinder head temperature C7
Cylinder head temperature C8
9
25, 26
Hot gas temperature COP monitoring (only possible for systems with up to 8 compressors)
10
27, 28
Suction gas superheat LT
11
29, 30
Gas cooler outlet temperature 2
12
31, 32
Gas cooler outlet temperature 1
13
33, 34
Suction gas superheat NT
7 x sensors / other
1
35
36
37
Low pressure transmitter
+ 24 V DC
4..20 mA
GND
2
38
39
40
Retrieval of the high pressure valve (HPV) opening degree
+ 24 V DC
4..20 mA
GND
3
41
42
43
Low pressure transmitter Z2
+ 24 V DC
4..20 mA
GND
4
44
45
46
High pressure transmitter
+ 24 V DC
4..20 mA
GND
5
47
48
49
Medium pressure transmitter
+ 24 V DC
4..20 mA
GND
6
50
51
52
HR request or external t
0
shift
+ 24 V DC
0..10 V
GND
7
61
59
60
Humidity sensor
+ 24 V DC
4..20 mA
GND
7.2.5 Connector Pin Assignment for Analogue Outputs
The analogue inputs for cylinder head temperature are limited to 8. These are distributed to NT/MP/LT
compressors in this order!
DANGER
Warning of dangerous electrical voltage! Danger of electric shock!
If voltage is applied to the
analogue inputs,
there is a danger of personal injury as the analogue inputs are not galvanically
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...