Firmware V1.41 V1
08.11.2022
146/219
Terminal No.
Function
No.
Basic module
SIOX 1
9
1, 2
-
Enable consumer or switching of FC compressor for compressor combined control
10
3, 4
-
Compressed gas desuperheater / Suction gas post-injection
5
6
7
8
13, 14
23, 24
33, 34
43, 44
-
Control of NT / MP compressor 1
Control of NT / MP compressor 2
Control of NT / MP compressor 3
Control of NT / MP compressor 4
5
6
-
13, 14
23, 24
Control of NT / MP compressor 5
Control of NT / MP compressor 6
7
-
33, 34
Controller Control of NT / MP compressor 7 or S1 spray system (function only available with a
SIOX)
8
-
43, 44
Control of NT / MP compressor 8 or S2 spray system (function only available with a SIOX)
.
Terminal No.
Function
No.
Basic module
SIOX 1
1
2
3
4
15,16, 18
25, 26, 28
35, 36, 38
45, 46, 48
-
Control of LT compressor 1
Control of LT compressor 2 control
Control of LT compressor 3
-
1
2
3
4
-
15,16, 18
25, 26, 28
35, 36, 38
45, 46, 48
Control of fan 1 *
Control of fan 2 *
Control of fan 3 *
Control of fan 4 *
.
Terminal No.
Function
No.
SIOX ejector
1
2
3
4
5
6
7
8
15,16,18
25, 26, 28
35, 36, 38
45, 46, 48
13, 14
23, 24
33, 34
43, 44
Gas ejector 1
Gas ejector 2
Gas ejector 3
Gas ejector 4
Gas ejector 5 / Liquid ejector 1 **
Gas ejector 6 / Liquid ejector 2
Gas ejector 7 / Liquid ejector 3
Gas ejector 8 / Liquid ejector 4
**A maximum of 8 ejectors can be connected, of which up to 8 can be gas ejectors and up to 3 can be liquid
ejectors
The gas ejectors are connected starting with terminal number 1, the liquid ejectors with terminal number 5 or
after the terminals occupied by gas ejectors.
Example 1: 5 gas ejectors and 2 liquid ejectors: Terminals 1 to 5 gas ejectors, terminals 6 and 7 liquid ejectors
Example 2: 3 gas ejectors and 3 liquid ejectors: Terminals 1 to 3 gas ejectors, terminals 5 to 7 liquid ejectors
1.
2.
3.
* Special features for the relay outputs for control of the fans:
With activated HP combined control, the relay outputs of the motor overload circuits for the
condenser fans can be used for monitoring the HP speed controller.
Fan control via relay is only possible if DIP switch 4 is set to OFF.
An additional analogue module is required for speed control of the fans; see
Modbus-Analogmoduls 0..10 V DC
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...