Firmware V1.41 V1
08.11.2022
144/219
Terminal No.
Function
No.
SIOX ejector
1
2
3
4
5
6..12
50, 51
52, 53
54, 55
56, 57
58, 59
RESERVE
Accumulator sensor 1 (bottom)
Accumulator sensor 2
Accumulator sensor 3
Accumulator sensor n (top)
Status of the oil management => oil shortage
1.
2.
3.
* Special features for the digital inputs for control of the condenser fans:
When HP combined control is active, the digital inputs of the motor overload cutouts for the
condenser fans can be used for monitoring the HP speed controller.
For "parallel" or "stages" combined control, the digital input of the motor overload cutout n (n =
number of fans +1) is used for the monitoring of the FC speed controller.
From V1.30: If the HR operation is deactivated (parameter HR operation = N, menu 3-2-2-3) or if
the status of the HR operation is sent via CAN bus, then digital input 21 (terminals 90, 91) can be
used to monitor a condenser fan motor.