Firmware V1.41 V1
08.11.2022
142/219
•
•
Connection to the power supply
In order to fuse the mains power line, a circuit breaker with the following characteristics is recommended:
Rated current for 230 V AC:
6 A
Tripping characteristic (type):
B
Connection cable requirements
As the controller is not equipped with an integrated disconnecting device in the form of a power switch, the
following must be implemented:
a) a switch or circuit breaker must be installed in the system or building installation,
b) this must be suitably positioned and easily accessible for the user, and
c) must be labelled as a disconnecting device for the equipment.
7.2.2 Terminal assignment of the 230 V AC digital inputs
Connection
: On the basic module terminal block upper right - 24 digital inputs
Connection
: On the SIOX extension module – terminal block upper right – 12 digital inputs
DANGER
Warning about dangerous electrical voltage! Danger of electric shock! BEFORE
connecting and
disconnecting, it must be ensured that
no voltage
is present at all connections of the controller.
Wiring of the digital inputs:
all digital inputs must be set to 230 V AC for the operation!
If 230 V AC is applied to an input that has been configured for 24 V AC, this results in destruction of the
module.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...