Firmware V1.41 V1
08.11.2022
130/219
5. Relay output for the base load rotation of the speed-controlled compressor for compressor
combined control
As the speed-controlled compressor in the combined control type of control shows the longest operating time,
base load rotation of the speed-controlled compressor is performed as well as the base load rotation of the
fixed-speed compressors. Compressor 1 and compressor 2 are alternately switched to the frequency converter
for this using the configurable cycle time for the base load rotation.
The base load rotation of the speed controlled compressor is triggered via the relay output 9 (terminals 1/2).
If the contact is closed, it must be ensured by external wiring that compressor 2 is switched to the frequency
converter and compressor 1 is in fixed-speed operation. If the contact is open, compressor 1 is assigned to the
frequency converter and compressor 2 on the mains power supply.